Universal fan coil unit/wall mounted split type fan coil

Split fan coil unit detail
             
Model HLC~ 51G 68G 85G 102G
Air flow m3/h 510 680 850 1020

Cooling capacity
W 2800 3700 4700 5600
BTU 9556 12628 16041 19113

Heating capacity
W 4190 5490 6930 8220
BTU 14300 18737 23652 28055
Water flow kg/h 600 770 960 1190
Input Power W 52 62 76 96
Noise level dB(A) 39 41 43 45
Pressure of outlet 12Pa
Power 220V/1 50HZ
Insulated grade E
Heating discharge fin Vertical blinds style
WA
Quantity of the Motor
1 1 1 1
WM
Quantity of the Fan
2 2 2 2
LA Water inlet pipe DN20 internal thread
LM Water outlet pipe DN20 internal thread
Condenser pipe DN20 internal thread

Dimension:
Dimension:          
Model HLC-51G HLC-68G HLC-85G HLC-102G  
A 850 850 1030 1080  
B 290 290 290 330  
C 180 180 185 215  
           
Remark: it is DN20 for both inlet/outlet water pipes and Condenser pipe.

 
Note:
1. Cooling: Indoors DB 27°C,WB 19.5°C; Chilled water inlet/outlet temp. 12°C/7°C.
2. Heating: Indoors DB WB 21°C, heating water inlet&outlet temperature 60°C/50°C;
3.The noise level based on: background noise 11.5Db(A) semi-anechoic room.  
4. Water resitance refers to that of rated water flow volume; 5. Input power refers to that of High speed air flow;
6. Above parameters are for your reference to model choice of FCU with cooling and heating; Heating energy of one row is 40% of three rows'; Low static pressure air flow volume loss: 10%, high static pressure air flow volume loss: 20%.
 